Product Categories
Isolator, black terminal
It converts various DC current signals into the required DC signals, achieves direct electrical isolation between signals, eliminates ground loops and reduces interference, and also provides high-voltage protection and surge suppression.
Business Inquiry:+86-15617410151
E-mail:848665210@qq.com
Product Overview
Specifications, Model, and Code
HX-WP-GLY-□□
Active isolation module
Input signal
1.0–10 mA DC
2.4–20 mA DC
3.1–5 VDC
4.0–10 VDC
5. Frequency
0. Other (thermal resistors, thermocouples)
Output signal
1.0–10 mA DC
2.4–20 mA DC
3.1–5 VDC
4.0–10 VDC
5. Frequency
0. Other ranges
Function: Converts various DC current signals into the required DC signal, achieves direct electrical isolation between signals, eliminates ground loops and reduces interference, and also provides high-voltage protection and surge suppression.
Features: Compact size, ideal for dense mounting; DIN‑rail mountable, easy to install and remove; high isolation performance and strong anti‑interference capability; high conversion accuracy and stable operation.
Key Technical Specifications
◆ Input resistance: 100 Ω when the input current is 0–5 mA DC.
At 0–10 mADC, 40 Ω
At 4–20 mA DC, 50 Ω
At 0–20 mA DC, 40 Ω
◆ Accuracy: ±0.5% F·S
◆ Temperature Drift: ≤±0.15%F·S/10℃
| Output signal | Load |
|---|---|
| 0–5 mA DC | 3 kΩ (maximum) |
| 0–10 mADC | 1.5 kΩ (maximum) |
| 4–20 mA DC | 750 Ω (maximum) |
| 0–20 mA DC | 750 Ω (maximum) |
| 0–2 VDC | 2 kΩ (minimum) |
| 0~5VDC | 5 kΩ (minimum) |
| 1–5 VDC | 5 kΩ (minimum) |
| 0–10 VDC | 10 kΩ (minimum) |
| -10 to +10 VDC | 10 kΩ (minimum) |
◆ Response time: ≤0.5 seconds (at 0–90% of output)
◆ Insulation Resistance: ≥100 MΩ at 500 VDC between input, output, and power supply
◆ Insulation Strength: 1500 VAC for 1 minute between input, output, and power supply.
◆ Output Protection: Unlimited output short-circuit protection
◆ Front-end adjustment: Zero-point and span adjustments within ±5% of full scale.
Installation and Usage
◆ Power supply: 24 VDC, with reverse polarity protection
◆ Sensor lead resistance: ≤5 Ω, with equal resistance among the three leads.
◆ Ambient temperature: -10℃ to +55℃
◆ Ambient humidity: 0–90% RH, non-condensing
◆ Housing: High-temperature-resistant, flame-retardant engineering plastic
◆ Mounting method: DIN rail mounting; rail width: 35 mm
◆ Storage temperature: -25℃ to +85℃
◆ Weight: 120g
◆ Power-on stabilization time: 20 minutes
Principle schematic diagram

Terminal Numbers and Wiring Diagram

Negative External Dimension Drawing

关键词: Isolator, black terminal
Online Inquiry
If you are interested in our services, please fill out the form below, and we will contact you as soon as possible.
Related products
Recommended products
Isolator 8000
This series of modules is compact and conforms to the internationally standard DIN rail mounting format, offering an exceptionally high performance‑to‑price ratio. Built using advanced SMD technology, they deliver highly reliable and stable operation, making them an ideal interface unit for smart controllers and DCS systems.
Wechat