Smart Digital Display Isolator


所属分类: Smart meter

所属分类: Product Center


Business Inquiry:+86-15617410151

E-mail:848665210@qq.com


Product Overview


Overview of the HXWP-20 Series Modules

I. General Technical Parameters of the HXWP-20 Series Modules

Input signal Analog output ·DC 0–10 mA (load resistance < 750 Ω)
·DC 4–20 mA (load resistance < 500 Ω)
·DC 0–5 V (load resistance ≥ 250 kΩ)
·DC 1–5 V (load resistance ≥ 250 kΩ)
Digital output Relay control output—relay ON/OFF with hysteresis. AC 220 V / 0.5 A; DC 24 V / 1 A (resistive load)
Communication Output Interface Type — Standard bidirectional serial communication interfaces: RS-485, RS-232C
Characteristics Measurement accuracy ±0.2%FS ±1 digit or ±0.5%FS ±1 digit
Resolution ±1 character
Measurement range -1999 to 9999 characters
Zero-point drift Input range: −100% to +100%
Source Resistance Below 500 Ω (effect on value: less than ±0.1% per 150 Ω)
Load resistor Less than 250 Ω (at a 1–5 V DC output)
Cold-Junction Compensation Error ±1℃
Open-circuit protection Open-circuit protection time: less than 2 s / FS
Operating environment Ambient temperature 0–50°C
Relative humidity ≤85% RH · Avoid strong corrosive gases
Supply voltage AC 90–265 V; DC 24 V ±10%
Power consumption ≤6W AC 220V power supply ≤6W DC 24V power supply

HXWP-201 (Single-channel) and 202 (Dual-channel) Voltage/Current Conversion Module

The HXWP20 voltage/current conversion module is a compact, plug-in‑type converter. It converts voltage (V or mV) and current (mA) signals into isolated 1–5 V DC or 4–20 mA DC output signals that are proportional to the input.

I. Instrument Features

1. Internally, a microprocessor performs mathematical computations, enabling highly accurate linearization of various nonlinear input signals. When paired with the HXWP20SH display module, the measured value corresponding to the input signal can be displayed digitally in a convenient and intuitive manner.

2. Optional AC or DC power supply; the transmitter output is isolated from the host unit, with selectable 1–5 V DC or 4–20 mA DC output signals and open‑circuit protection.

II. Instrument Parameters and Wiring Diagram

Model number HX-WP-201 202 Thermocouple/RTD Series
Input signal Analog quantity Thermocouples: Standard thermocouples—B, S, K, E, J, T, WRe, etc.
Resistance thermometer: Standard platinum resistance thermometer: Pt100, 3-wire connection
Standard copper resistance thermometers: Cu50, Cu100, 3-wire connection
Characteristics Response time Approximately 500 ms
  A: Single-channel thermocouple input type B: Single-channel thermoresistor input type
 
  C: Dual-channel thermocouple input type D: Dual-channel thermoresistance input type
 

Note:
1. The external connection terminal is an M3.5 screw. Use non-soldered crimp terminals for the connection.
2. An external power switch and fuse shall be installed. A 0.5 A fuse is recommended (use a fast‑acting type when operating on a 24 VDC power supply).
3. The instrument is equipped with overcurrent protection to prevent damage caused by internal power‑supply short circuits.
4. In environments subject to lightning strikes, please install a dedicated surge arrester.

III. Product Range Table for the HXWP-LED Series Thermocouple/Resistance Temperature Detector Transmitters

HXWP-201 (Single-channel) 202 (Dual-Channel) Power Distribution Module

The HXWP20-type distribution module is a compact, plug-in‑type conversion module. It supplies power to two‑wire transmitters while receiving from them 4–20 mA DC output signals that are proportional to differential pressure, pressure, liquid level, and other process variables.

I. Instrument Features

It supports both AC and DC power supplies, features galvanic isolation between the transmitter output and the host unit, offers a selectable output signal of either 1–5 V DC or 4–20 mA DC, and is equipped with a transmitter power switch.

II. Instrument Parameters and Wiring Diagram

Model number HXWP-201 202 Series Distribution Module
Input signal Analog quantity 4–20 mA DC
Characteristics Response time Approximately 500 ms (time constant) for V and mA inputs: approximately 100 ms (time constant)
Wiring diagram A: Single-channel input type B: Dual-input type
 

III. Distribution Module Family Table

★ Code example: HX-WP-201-DL-14-11-A-W

Single-channel, with an input signal of 0–20 mA; the first output is 1–5 V, and the second output is also 1–5 V. Both outputs are galvanically isolated, powered by DC 24 V.

关键词: Smart Digital Display Isolator

Online Inquiry

If you are interested in our services, please fill out the form below, and we will contact you as soon as possible.

Related products

Recommended products


Liquid Crystal Flow Totalizer

Flashing alarm

Isolator, black terminal

It converts various DC current signals into the required DC signals, achieves direct electrical isolation between signals, eliminates ground loops and reduces interference, and also provides high-voltage protection and surge suppression.

Isolator 8000

This series of modules is compact and conforms to the internationally standard DIN rail mounting format, offering an exceptionally high performance‑to‑price ratio. Built using advanced SMD technology, they deliver highly reliable and stable operation, making them an ideal interface unit for smart controllers and DCS systems.